一起平衡绕组接线错误引起的主变冲击合闸失败分析

Failure Analysis of Main Variable Impact Close Caused by Error of Balancing Wrap Connection

  • 摘要: 为了提高主变大修、技改后送电的成功率和故障排查的准确率,本文以某主变大修冲击合闸不成功实际案例介绍了主变冲击合闸时比率差动保护动作情况,利用一种新的电压法分析了故障的排查及故障准确定位并对其故障原因进行验证,同时针对平衡绕组因接线、匝间短路问题提出了预防事故的建议措施

     

    Abstract: In order to improve the success rate of power transmission and the accuracy of fault troubleshooting after the main transformer overhaul and technical modification, this paper introduces the ratio differential protection action during the impact closing of the main transformer overhaul with a practical case of unsuccessful impact closing. A new voltage method is used to analyze the fault troubleshooting and accurate fault location, and the fault causes are verified. At the same time, the suggestions to prevent accidents are put forward for the problems of wiring and short circuit between turns in the balance winding.

     

/