10kV配网线路避雷器接地方式和配置方案研究

The Research on grounding Mode and configuration Scheme of Linghtning ar-rester in 10kV Distribution Line

  • 摘要: 10kV架空线路在配电网中占了较大的比例,由于其绝缘水平较低,据统计,感应过电压是造成配电线路雷击跳闸故障的主要原因。线路避雷器是目前降低配电线路雷击跳闸率最有效手段之一,而线路避雷器的接地方式,尤其使用比较多的水泥杆的接地方式,以及避雷器的配置方案直接影响配网线路防雷效果和耐雷水平。本文通过PSCAD软件建立10kV配电线路的感应雷过电压仿真计算模型,分析验证避雷器采用杆塔自然接地可行性和有效型,以及研究接地电阻大小和避雷器安装密度对配电线路感应雷耐雷水平的影响, 验证了水泥杆采用自然接地方式的可行性,提出了合理的避雷器配置方案,确保了线路防雷保护效果和技术经济性。

     

    Abstract: 10kV overhead line accounts for a large proportion in the distribution network. Due to its low insulation level, according to statistics, induced overvoltage is the main cause of lightning trip in distribution lines.The line arrester is one of the most effective means to reduce the lightning trip rate of distribution line at present, the grounding method of the lightning arrester and the configuration plan of the line arrester directly affect the lightning protection effect and lightning resistance level of distribution line.This paper was established Simulation model of induced lightning overvoltage of 10 kv distribution line through PSCAD software, analysis and verify the feasibility and effective of natural grounding type with tower, and the influence of the value of ground resistance and the installation density of arrester on the induced lightning resistance level of distribution lines were  studied.The feasibility of natural grounding method for concrete pole is verified, and a reasonable lightning arrester configuration scheme was put forward to ensure the lightning protection effect and technical economy of the line.

     

/