220kV双母线接线母联间隔电流互感器异常时隔离与恢复送电分析

Analysis of isolation and power transmission recovery of 220kV double-busbar bus-link current transformer under abnormal condition

  • 摘要: 220kV双母线接线方式下,两条母线经由母联间隔并列运行,当母联间隔设备出现异常时,对双母线运行影响极大,故障隔离方式直接影响故障处置及时性、双母线上运行的线路及地区电网运行方式,处置不当可能造成母线全停,甚至地区电网解列,直接威胁设备、电网安全稳定运行。本文通过一起500kV超高压变电站220kV母联间隔电流互感器异常隔离与恢复送电实际案例,对三种隔离处置及恢复送电方式优缺点进行分析,为该类故障处置提供一定参考。

     

    Abstract: Under 220 kV double-busbar connection mode, two busbars run in parallel through busbar interval. When the equipment of busbar interval is abnormal, it has great influence on double-busbar operation, the fault isolation mode directly affects the timeliness of fault treatment, the operation mode of lines and regional power grids on double-busbars, and improper treatment may cause all busbars to stop, or even the regional power grids to disintegrate, it directly threatens the safe and stable operation of equipment and power grid. This paper analyzes the advantages and disadvantages of three types of isolation treatment and restoration power transmission through an actual case of abnormal isolation and restoration power transmission of 220 kV busbar current transformer in a 500 kV ehv substation, it provides some reference for the treatment of this kind of fault.

     

/