一起TA不完全星形接线造成的主变 越级跳闸事件分析

Analysis of a Main Transformer Trip Event Caused by Incomplete Star Connection of TA

  • 摘要: 现阶段变电站35kV及以下不接地系统电流互感器多采用两相不完全星形接线,正常情况下保护、测量采集AC相电流,B相电流通过AC相电流的向量和计算出来,其能反映各种相间短路故障,但保护的灵敏度相比于三相完全星型接线方式较差,由于其减少了三分之一的设备,节约较大成本,所以在不接地系统中应用较为广泛。本文通过分析一起因两相不完全星形接线电流互感器回路异常造成主变越级跳闸的案例来进一步认识其接线方式在工作期间存在的多样性问题,以便于类似故障分析及相关防范措施的制定。

     

    Abstract: At At present, the current transformers in the non-earthing system of 35 kv and below in substations usually adopt two-phase incomplete star connection, the b-phase current is calculated by the vector sum of the AC-phase current, which can reflect various short-circuit faults between phases, but the sensitivity of the protection is worse than that of the three-phase full-star connection, because it reduces the equipment by one third, therefore, it is widely used in ungrounded system. In this paper, a case of main transformer skip trip caused by two-phase incomplete star-shaped current transformer circuit abnormality is analyzed to further understand the diversity of its wiring mode during working, in order to facilitate similar failure analysis and related preventive measures.

     

/

返回文章
返回