投稿入口

6kV真空接触器分闸固有延时测试及其保护配合整定方法的研究与应用

Research and Application of Opening Inherent Delay Test and Protection Coordination Setting Method for 6kV F-C

  • 摘要: 针对6kV真空接触器在合闸瞬间发生接地短路故障的极端条件下会出现较长的分闸固有延时现象,造成保护发生越级跳闸的安全隐患问题。本文提出了一种6kV真空接触器分闸固有延时测试及其保护配合整定方法,通过分析真空接触器的控制回路接线和保护整定值情况,结合试验设计与安全措施执行,真实模拟出开关合闸于接地短路故障时的动作分闸情况,进而使真空接触器分闸固有延时与零序保护动作时间整定值的匹配性关系得到校核,避免了开关在合闸瞬间发生接地短路故障时因开关分闸固有延时问题而导致保护越级跳闸,提高了设备运行的可靠性,为合理设定开关的零序保护动作时间定值提供了有力的指导依据。

     

    Abstract: In view of the extreme conditions of 6kV F-C in the ground short circuit fault at the moment of closing, there will be a long inherent delay phenomenon of opening, resulting in the safety hazard problem of protecting the occurrence of leapfrog tripping. In this paper, a 6kV F-C opening inherent delay test and its protection coordination tuning method are proposed. By analyzing the wiring and protection setting value of the control loop of the F-C, combined with the experimental design and the execution of safety measures, the action opening situation of the switch closing in the ground short circuit fault is truly simulated. The matching relationship between the inherent delay of the opening of the F-C and the setting value of the zero-sequence protection action time was further checked, avoid the protection trip due to the inherent delay problem of the switch opening when the switch is closed with a ground short circuit fault at the moment of closing, improved reliability of equipment operation, it provides a strong guiding basis for reasonably setting the zero sequence protection action time setting of the switch.

     

/

返回文章
返回