一起线路两侧电流回路接线不一致造成区外故障线路差动保护误动作分析及预防

Analysis of main transformer differential trip caused by electric welding

  • 摘要: 通过对一起线路两侧电流回路接线不一致造成区外故障是导致线路差动保护误动作的分析,得出原因是线路一侧的保护装置采用A、C相电流作为本侧保护电流,线路的另一侧采用A、B、C三相电流作为本侧保护电流,正常运行时因线路负荷较小,线路两侧保护装置未告警、动作,区外故障时造成该线路两侧线路差动保护误动作。通过案例分析,介绍了相关的应对措施和处理办法,为后续类似事件的处理提供参考依据。

     

    Abstract: This paper introduces an accident of the first protection differential protection action and the second protection starting unaction of a main transformer caused by an external fault of a 110 kv substation, the cause of the first set of protection differential protection action of the main transformer is the three-phase short-circuit grounding fault of the 10 kv line on the low-voltage side of the substation, at the same time, the main transformer's first set of protection for the 10 kv side B phase differential current circuit is damaged at the secondary terminal connection of the current transformer, the current sampling of the first differential current circuit of the main transformer in 10 kv line fault is incorrect, which is not consistent with the current increase of 110 kv side and 35 kv side, cause the first set of protection ratio differential protection b-phase action jump off the main transformer three-side switch. According to the actual situation of the site and the analysis of the cause of action, the relevant solutions are put forward, which provide a reference for the prevention and solution of similar accidents.

     

/

返回文章
返回